Circuit Protection
Q. Circuit Protection and the 17th Edition of the IEE Regulations
Circuit Protection and the 17th Edition of the IEE Regulations
For 17th Edition Consumer Units including the Chint High Integrity Variant please click this link
With the introduction of the 17th edition major changes came in to force, particularly in the area of Earth Leakage Protection. The following can only be a summary, full and detailed information should be obtained from the regulations.
Installations should be so designed as to offer proper circuit discrimination so as to ensure maximum safety/convenience in the event of 1 circuit failure, this is particularly important in the case of lighting circuits.
Summary
- Regulation 411.3.3: All socket outlets meant for use by an ordinary peron with a rated current not exceeding 20 amps should be protected by a 30mA RCD.
- Regulation 701.411.3.3: All circuits in a room with a fixed bath or shower should be protected by 1 or more 30mA RCDs.
- Regulation 522.6.6, 522.6.7 and 522.6.8: All cables buried beneath a plaster surface of a wall at less than 50mm should be protected by 30mA RCDs.
- Regulation 411.3.3: All cables installed in metal stud partition walls should be protected by 30mA RCDs.
The following summary table refers to additional protection, generally this is additional to MCBs - Fuses, i.e. earth leakage protection. Today SP (Single Pole) RCBOs are seen as a convenient method of offering both overload and Earth leakage protection from one device.
Summary Table
For 17th Edition Consumer Units please click this link
| Regulations | Relating to | Examples | Additional Protection |
| 411.3.3 | Sockets up to 20a rating for general use by ordinary persons |
| 30mA RCD |
| 701.411.3.3 | All circuits in a room witha fixed bath or shower |
| 30mA RCD |
| 522.6.6 522.6.7 and 522.6.8 | All circuits buried in a wall or partition at less than 50mm and without mechanical protection |
| 30mA RCD |
Q. what are the required electrical cable sizes for 7/8/9/10 kw electric showers.ie 6mm/10mm
There are a number of factors to be taken in to consideration when determining the correct size of cable, what is the length of run, how is the cable being run, vol drop etc. For this reason we do not give specific advice as it should be left to a qualified electrician. However, as a rule of the thumb for general guidance only: 7/8kw - 6mm T&E up to 20m 9/10kw - 10mm T&E up to 20m
Disclaimer- This is general guidance and not meant as a definitive answer as each installation should be considered individually including how the cable is to be run. If in doubt consult a qualified electrician before you make a purchase.





