Customer service available: 9am - 4pm Monday to Friday Call Us now
More Contact Info

ESP Fireline 4 Zone Fire Alarm Panels

ESP Fireline 4 Zone Fire Alarm Panels

Availability: In stock

ESP Fireline Mag range of fire alarm panels which includes a 4 zone fire alarm panel enclosed in a polycarbonate or metal container.
ESP Fireline 4 Zone Fire Alarm Panel - Polycarbonate

ESP Fireline 4 Zone Fire Alarm Panel - ABS Casing

From £93.61 Incl. Tax: £112.33
Availability: 10
SKU: MAG4P
ESP Fireline 4 Zone Fire Alarm Panel - Polycarbonate

ESP Fireline 4 Zone Fire Alarm Panel - Metal Casing

From £93.61 Incl. Tax: £112.33
Availability: 2
SKU: MAG4
OR
Description

ESP Fireline Mag 4 Zone Fire Alarm Control Panels

The MAG range is simple to install, program and expand, which makes for a perfectly easy job for installers. Users will find the MAG Alarm Centres very straightforward, the instructions are very clear and easy to follow. The key words associated with the MAG range are PERFORMANCE, QUALITY AND RELIABILITY. It has been conscientiously designed, in order to suit the needs and demands of users, specifiers and installers alike. Specifiers will be pleased with the number of great features this MAG Alarm Centre offers, along with being designed into a cleverly assembled package.

Features

    • 4 programmable zones
    • Activate end of line monitoring and head removal
    • 30 fire detectors per zone
    • Unlimited number of call points per zone
    • Integral evacuate alarm button
    • Class change facility
    • Enable/disable security key
    • One man walk test facility
    • Fire volt free change over relay
    • Fault volt free change over relay
    • Individual sounder circuit fault ID
    • Individual zone/sounder isolate
    • BS5839 and EN54 P2/4 compliant
    • CE certified
    • Requires only 1x12v battery (See associated products)
    • ABS casing (MAG4P)
    • Metal casing (MAG4)
       

Specifications

    MAG4P MAG4
 INPUTS  Max detectors per zone  30 30
   Thresholds for zone conditions  0-2 mA (Fault condition)
 2-6 mA (Normal condition)
 6-110 mA (Fire condition)
 110 mA Short (Fault condition)
0-2 mA (Fault condition)
2-6 mA (Normal condition)
6-110 mA (Fire condition)
110 mA Short (Fault condition)
 POWER  Mains fail consumption  50mA 50mA
   Mains Supply  230 VAC ± 10% 230 VAC ± 10%
   Standby supply  1 x 12V S.L.A Battery (upto 8ah) 1 x 12V S.L.A Battery 
   Power availability  0.7 amps 0.7 amps
 OUTPUTS  Sounder 1  24V (max 300mA fused) 24V (max 300mA fused)
   Sounder 2  24V (max 300mA fused) 24V (max 300mA fused)
   Fault Relay  Volt free 500mA (maximum load) Volt free 500mA @ 24V (maximum load)
   Auxiliary output  24VDC (300mA fused) 24VDC (300mA fused)
 ENVIRONMENT  Working Temperature  0 to 40°C 0 to 40°C
   Storage Temperature  -20 to 60°C  -20 to 60°C
   Humidity  0-95% 0-95%
   Dimensions (mm)  340W 290H 100D 320W 220H 80D
   Weight  3.5KG 3.5KG

 Downloads

MAGPro Fireline Catalogue